LionRock generator sets are suitable for various fields such as commercial, industrial, telecommunications, data centers, and infrastructure.
Product Features
Fixed shaft driven cooling water tank
Standard cooling system at 40 ° C
rubber shock absorber
Configure base fuel tank (below 700kVA)
High temperature and rotating components (such as smoke exhaust and fans) have protective covers on the water tank
Equipped with exhaust bellows and industrial muffler
Equipped with a 12/24VDC starter motor and battery
The generator set has passed CE certification
Standard 3-pole output circuit breaker
Coolant drain valve and oil drain valve
The Lion Rock generator sets have undergone load tests at 0%, 25%, 50%, 75%, 100%, and 110% rated power.
quality standard
All generator sets comply with international standards, including ISO 8 5 2 8, ISO3046, IEC60034, BS5000
Certified with ISO9001, ISO14001, and ISO45001
Having a CE certificate for generator sets
Definition of rated power according to ISO8528 standard
Common power - Under variable loads, the load rate does not exceed 70% of the rated power, and there is no limit to its annual operating time. An overload of 10% is allowed for 1 hour every 12 hours of operation.
Backup power - can output under different loads. The average power is 80% of the rated standby power, and the annual operating time is not more than 500 hours. Overloading is not allowed.